AsymDelay
denotes asymmetry which is defined as transmission delay minus receive
delay. If fixed asymmetry is known,
Echo
synchronization method can be used,
provided that
AsymDelay
is properly set. From the definition follows that asymmetry is
always positive at one end and negative at the other end.
MaxTransmDelay
indicates maximum transmission delay. Data for maximum 40 ms
transmission delay can be buffered up. Delay times in the range of some ms are
common. If data arrive in wrong order, the oldest data is disregarded.
MaxtDiffLevel
indicates the maximum time difference allowed between internal clocks
in respective line ends.
64 kbit mode specific settings
TransmCurr
is used to select among the following:
•
one of the two possible local currents is transmitted
•
sum of the two local currents is transmitted
•
channel is used as a redundant backup channel
breaker-and-a-half arrangement has two local currents, and the Current Transformer
(CT) grounding for those can differ.
CT-SUM
transmits the sum of the two CT groups.
CT-DIFF1
transmits CT group 1 minus CT group 2 and
CT-DIFF2
transmits CT group
2 minus CT group 1.
CT-GRP1
and
CT-GRP2
transmit the respective CT groups, and setting
RedundantChannel
determines that the channel is used as a redundant backup channel.
The redundant channel takes the CT group setting of the main channel.
RemAinLatency
corresponds to
LocAinLatency
set in the remote IED.
AnalogLatency
specifies the time delay (number of samples) between actual sampling
and the time the sample reaches LDCM. The value is set to 2 when transmitting analog
data. When a merging unit according to IEC 61850-9-2 is used instead of the TRM,
this parameter shall be set to 5.
CompRange
value indicates the current peak value over which truncation is made. To
set this value, knowledge of fault current levels is required. It is recommended to set
the minimum range that will cover the expected fault current value. For example, if a
40kA fault level is expected on the network, the 0-50kA settings range should be
chosen.
2 Mbit mode specific settings
1MRK 505 370-UUS A
Section 18
Remote communication
Busbar protection REB670 2.2 ANSI
497
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...