TimeSynch
M11348-167 v15
When the source of the time synchronization is selected on the local HMI, the
parameter is called
TimeSynch
. The time synchronization source can also be set from
PCM600. The setting alternatives are:
FineSyncSource
which can have the following values:
•
Disabled
•
SPA
•
LON
•
BIN
(Binary Minute Pulse)
•
GPS
•
GPS+SPA
•
GPS+LON
•
GPS+BIN
•
SNTP
•
GPS+SNTP
•
IRIG-B
•
GPS+IRIG-B
•
PPS
CoarseSyncSrc
which can have the following values:
•
Disabled
•
SPA
•
LON
•
DNP
•
IEC 60870-5-103
The function input to be used for minute-pulse synchronization is called BININPUT.
For a description of the BININPUT settings, see the
Technical Manual
.
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
The parameter
SyncMaster
defines if the IED is a master, or not a master for time
synchronization within a Substation Automation System, for IEDs connected in a
communication network (IEC 61850-8-1). The
SyncMaster
can have the following
values:
•
Disabled
•
SNTP -Server
Section 20
1MRK 505 370-UUS A
Basic IED functions
520
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...