FunctionMode
This parameter can be set
Current
or
Contact
. This states the way the
detection of failure of the breaker is performed. In the mode current the current
measurement is used for the detection. In the mode
Contact
the long duration of
breaker position signal is used as indicator of failure of the breaker. The mode
Current/
Contact
means that both ways of detections are activated.
Contact
mode can be usable
in applications where the fault current through the circuit breaker is small. This can be
the case for some generator protection application (for example reverse power
protection) or in case of line ends with weak end infeed.
RetripMode
: This setting states how the re-trip function shall operate.
Retrip Off
means
that the re-trip function is not activated.
CB Pos Check
(circuit breaker position check)
and
Current
means that a phase current must be larger than the operate level to allow
re-trip.
CB Pos Check
(circuit breaker position check) and
Contact
means re-trip is
done when circuit breaker is closed (breaker position is used).
No CBPos Check
means
re-trip is done without any check of breaker position.
Table 32:
Dependencies between parameters RetripMode and FunctionMode
RetripMode
FunctionMode
Description
Retrip Off
N/A
the re-trip function is not
activated
CB Pos Check
Current
re-trip is done if the phase
current is larger than the operate
level after re-trip time has
elapsed
Contact
re-trip is done when auxiliary
contact position indicates that
breaker is still closed after re-trip
time has elapsed
Current/Contact
both methods according to above
are used but taken into account
also
I>BlkCont
No CBPos Check
Current
re-trip is done without check of
current level
Contact
re-trip is done without check of
auxiliary contact position
Current/Contact
re-trip is done without check of
current level or auxiliary contact
position
BuTripMode
: Back-up trip mode is given to state sufficient current criteria to detect
failure to break. For
Current
operation
2 out of 4
means that at least two currents, of
the three-phase currents and the residual current, shall be high to indicate breaker
failure.
1 out of 3
means that at least one current of the three-phase currents shall be
high to indicate breaker failure.
1 out of 4
means that at least one current of the three-
phase currents or the residual current shall be high to indicate breaker failure. In most
Section 7
1MRK 505 370-UUS A
Current protection
216
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...