Circuit breaker status
Monitoring the breaker status ensures proper functioning of the features within the
protection relay such as breaker control, breaker failure and autoreclosing. The breaker
status is monitored using breaker auxiliary contacts. The breaker status is indicated by
the binary outputs. These signals indicate whether the circuit breaker is in an open,
closed or error state.
Remaining life of circuit breaker
Every time the breaker operates, the circuit breaker life reduces due to wear. The wear
in a breaker depends on the interrupted current. For breaker maintenance or
replacement at the right time, the remaining life of the breaker must be estimated. The
remaining life of a breaker can be estimated using the maintenance curve provided by
the circuit breaker manufacturer.
Circuit breaker manufacturers provide the number of make-break operations possible at
various interrupted currents. An example is shown in figure
Section 14
1MRK 505 370-UUS A
Monitoring
444
Busbar protection REB670 2.2 ANSI
Application manual