zone the outgoing current is used as stabilizing current instead of total incoming
current in order to guarantee the check zone operation for all possible operating
conditions in the station. The check zone operating characteristic is shown in Figure
. Note that the check zone minimum differential operational level
OperLevel
shall be
set equal to or less than the corresponding operating level of the usual discriminating
zones.
IEC06000062-2-en.vsdx
OperLevel
Slope (settable)
I
out
[Primary Amps]
I
d
[
P
ri
m
a
ry
A
m
p
s
]
Operate
region
IEC06000062 V2 EN-US
Figure 42:
Check zone operation characteristic
The built-in check zone feature has to be enabled (that is, setting parameter
Operation
shall be set to
On
) in order to fully enable the check zone. For substations where
traditional “CT switching” is not required (that is, single busbar station or one-and-half
breaker station), a check zone must not be used. For such applications, the check zone
shall be disabled by the setting parameter
Operation
to
Off
.
The check zone measures only the currents from the bays which leaves the station.
Exactly which CTs shall be measured by the check zone varies, depending on the
version of the IED used:
•
In two-zone busbar differential protections, it is freely settable by using the setting
CheckZoneSel
at each bay function block.
•
In six-zone busbar differential protection, the currents of all active feeder bays are
measured unconditionally by the check zone, if the check zone is able to operate.
By an active feeder, we mean a feeder bay which is not deactivated, that is, neither
its
operMode
is
Off
nor it is out of service.
And the check zone supervises differential protection zones. Exactly which differential
protection zones shall be supervised by the operation of the check zone also varies,
depending on the version of the IED used:
1MRK 505 370-UUS A
Section 6
Differential protection
Busbar protection REB670 2.2 ANSI
115
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...