Set the course time synchronizing source (
CoarseSyncSrc
) to
Disabled
when GPS time synchronization of line differential function is used. Set
the fine time synchronization source (
FineSyncSource
) to
GPS
. The
GPS will thus provide the complete time synchronization. GPS alone
shall synchronize the analogue values in such systems.
IEEE 1588 (PTP)
GUID-424227EC-74A1-4628-8948-C1876840ABFE v2
Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration
tool /ECT) in PCM600.
PTP
can be set to
On
,
Off
or
Slave only
. When set to
Slave only
the IED is connected to
the PTP-group and will synchronize to the grandmaster but cannot function as the
grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To set
one IED as the grandmaster change Priority2 to 127 instead of the default 128.
IEC16000089-1-en.vsdx
IEC16000089 V1 EN-US
Figure 216:
Enabling PTP in ECT
The
PTP VLAN
tag must have the same value in station clock and in the IED. The
default value is set to 0.
The
PTP VLAN
tag does not need to be the same on all access points in one IED. It is
possible to mix as long as they are the same for all devices on each subnet.
1MRK 505 370-UUS A
Section 20
Basic IED functions
Busbar protection REB670 2.2 ANSI
521
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...