en04000487_ansi.vsd
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
AB_TRAFO
ABC_BC
AB_TRAFO
ABC_BC
(WA1)A1
(WA2)B1
(WA7)C
C
B2
A2
ANSI04000487 V1 EN-US
Figure 152:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic for input signals concerning bus-coupler are the same as the
specific logic for the line bay (ABC_LINE):
Signal
BC_12_CL
A bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12
The switch status of BC_12 is valid.
EXDU_BC
No transmission error from bus-coupler bay (BC).
The logic is identical to the double busbar configuration “Signals from bus-coupler“.
12.4.4.3
Configuration setting
M13566-22 v5
If there are no second busbar B and therefore no 289 disconnector, then the
interlocking for 289 is not used. The state for 289, 2189G, BC_12 are set to open by
setting the appropriate module inputs as follows. In the functional block diagram, 0 and
1 are designated 0=FALSE and 1=TRUE:
•
289_OP = 1
•
289QB2_CL = 0
•
2189G_OP = 1
•
2189G_CL = 0
•
BC_12_CL = 0
•
VP_BC_12 = 1
Section 12
1MRK 505 370-UUS A
Control
376
Busbar protection REB670 2.2 ANSI
Application manual