HarmBlockx
: This is used to enable block of step x from 2
nd
harmonic restrain
function.
tPCrvx, tACrvx, tBCrvx, tCCrvx
: Parameters for user programmable of inverse time
characteristic curve. The time characteristic equation is according to equation
:
[ ]
p
A
t s
B TD
i
C
ipickup
=
+
×
-
æ
ö
ç
÷
ç
÷
ç
÷
æ
ö
ç
÷
ç
÷
è
ø
è
ø
EQUATION1722 V1 EN-US
(Equation 36)
Further description can be found in the technical reference manual.
tPRCrvx, tTRCrvx, tCRCrvx
: Parameters for user programmable of inverse reset time
characteristic curve. Further description can be found in the technical reference
manual.
7.4
Four step directional negative phase sequence
overcurrent protection NS4PTOC (46I2)
GUID-E8CF8AA2-AF54-4FD1-A379-3E55DCA2FA3A v1
7.4.1
Identification
GUID-E1720ADA-7F80-4F2C-82A1-EF2C9EF6A4B4 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step negative sequence
overcurrent protection
NS4PTOC
I2
4
4
alt
IEC10000053 V1 EN-US
46I2
7.4.2
Application
GUID-343023F8-AFE3-41C2-8440-1779DD7F5621 v2
Four step negative sequence overcurrent protection NS4PTOC (4612) is used in
several applications in the power system. Some applications are:
Section 7
1MRK 505 370-UUS A
Current protection
204
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...