3.1.3
Configuration X02
SEMOD129275-120 v5
This configuration includes only busbar protection for double busbar-single breaker
stations, where Zone Selection is done by using a and b auxiliary contacts from every
disconnector and/or circuit breaker. Thus full disconnector/breaker supervision is
available. This configuration is available for only three REB670 variants (that is A31,
B21 and B31). It shall be noted that optional functions breaker failure protection
CCRBRF (50BF), end fault protection and overcurrent protection PH4SPTOC (51) can
be ordered together with this configuration, but they will not be pre-configured. Thus
these optional functions shall be configured by the end user.
3.1.4
Configuration X03
SEMOD129275-124 v5
This configuration includes BBP with breaker failure protection CCRBRF (50BF), end
fault protection and overcurrent protection PH4SPTOC (51) for double busbar-single
breaker stations, where Zone Selection is done by using a and b auxiliary contacts from
every disconnectors and/or circuit breakers. Thus full disconnector/breaker supervision
is available. This configuration is available for only three REB670 variants (that is
A31, B21 and B31).
In order to use X03 configuration, optional breaker failure and overcurrent functions
must be ordered.
3.1.5
Description of 3 ph package A20A
SEMOD129275-4 v8
Three-phase version of the IED with two low-impedance differential protection zones
and four three-phase CT inputs A20A. The version is intended for simpler applications
such as T-connections, meshed corners, and so on.
Section 3
1MRK 505 370-UUS A
Configuration
52
Busbar protection REB670 2.2 ANSI
Application manual
Summary of Contents for RELION REB670
Page 1: ...RELION 670 SERIES Busbar protection REB670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 24: ...18 ...
Page 40: ...34 ...
Page 72: ...66 ...
Page 102: ...96 ...
Page 266: ...260 ...
Page 272: ...266 ...
Page 290: ...284 ...
Page 432: ...426 ...
Page 542: ...536 ...
Page 552: ...546 ...
Page 553: ...547 ...