SCD file
do IED engineering
export SCD file
PCM600 (1)
create project
import SCD file
configure data sets
configure Report CBs
configure GOOSE CBs
export SCD file
IET600 (2)
import SCD file
link GOOSE input data
Write to IED
PCM600 (3)
SCD file
IED 1
IED n
IED 2
IED n-1
IEC11000264.vsd
IEC11000264 V1 EN-US
Figure 63: IEC 61850: Signal engineering procedure flow
7.3
Exporting SCL files from PCM600
GUID-2A07D447-0EC8-45BC-9C71-1A015F030C3F v4
A pre-condition is that all IEDs in the project must be engineered in PCM600. The hardware
interface, for example the communication port, has to be selected and configured. The used
interface addresses have to be set according to protocol and project definitions. The station
communication port has to be activated in the IED, that is to set the IEC61850-8-1
Operation
setting to
On.
7.3.1
Exporting SCD files
GUID-2FDA859B-3761-4310-BEFF-11BB046A406B v1
Procedure to export the SCD file from PCM600:
1.
Select the station in the plant structure, see
.
1MRK 511 284-UEN B
Section 7
IEC 61850 communication engineering
650 series
79
Engineering manual