IEC08000123.vsd
Symbol library
window
IED HMI
display window
HMI display
window pages
Regard the
squence of pages
IEC08000123 V1 EN-US
Figure 54: GDE: Screen image with active GDE
Procedure
1.
Start GDE to open a presentation of the tool.
2.
GDE has a fixed symbol library window on the left side of the display.
3.
The presentation is empty when no page exists for the IED.
Display window and sequence order
It is important to link correctly between the HMI display page and the
corresponding bay that is presented as a single line diagram on this HMI page.
Rules to handle HMI pages:
•
Several single line diagrams can be created for one bay.
•
The IED supports one bay.
•
The sequence order of the HMI pages in the Graphical Display Editor starts from left to
right.
•
Measurements and the single line diagram can be shown on the page in any possible order
and placement.
•
All symbol objects, for example apparatus, text and measurement, on the HMI page must
be linked to the correct function block in the application configuration in order to present
the correct process values.
Section 6
1MRK 511 284-UEN B
Local HMI engineering
62
650 series
Engineering manual
© Copyright 2013 ABB. All rights reserved