IEC08000336.vsd
IEC08000336 V1 EN-US
Figure 81: CMT: Context menu in DNP3 window
2.
The selection window shows the number of signals selected, see
.
IEC08000363.vsd
IEC08000363 V1 EN-US
Figure 82: CMT: Set Index menu
3.
Define the
Starting index for this group and click OK.
Procedure to set class configuration:
1.
Click in the class field of the signal to change the class configuration.
2.
The
Select Class window opens.
3.
Make the selection according to the definitions in the project and click
OK to close the
window and get the new configuration, see
IEC08000338.vsd
IEC08000338 V1 EN-US
Figure 83: CMT: Select Class window
9.4.1
Configuring DNP3 class
GUID-B46924F8-B960-4B79-8EB8-4DFADABDFB10 v1
In DNP3 the user classifies the signals and defines those signals that are not member of any
class. CMT has a default predefined organization of classes per signal type. In the master
station the classes can be polled in sequences according to the demands in the project.
Unsolicited reporting is possible as well.
Modify the organization of the classes for each signal individually.
1MRK 511 284-UEN B
Section 9
DNP3 communication engineering
650 series
95
Engineering manual
© Copyright 2013 ABB. All rights reserved