The station level is predefined by "AA1", where 1 is the index.
•
The voltage level is predefined by "J1", where 1 is the index.
•
The bay level is predefined by "Q01", where 01 is the index.
•
The IED is predefined by "A1", where 1 is the index.
The predefined full path name of the technical key for the IED would be AA1J1Q01A1.
For all practical engineering purposes (both towards the IED and towards the 61850
engineering process), the user should keep the default SCL technical key. It is however
possible, due to for example company naming policies, to rename the SCL technical key for the
station level, voltage level, bay level and IED level using the Object properties window as shown
in
.
•
The station level has been renamed as "DMSTAT"
•
The voltage level has been renamed as "C1"
•
The bay level has been renamed as "Q1"
•
The IED has been renamed as "SB1"
The renamed full path name of the technical key for the IED would be DMSTATC1Q1SB1.
IEC08000374.vsd
IEC08000374 V1 EN-US
Figure 17: PCM600: IEC 61850 signal designation concept
4.7
Inserting an IED
SEMOD58416-5 v7
The context menu or the
Object Types view shows the available 650 series IEDs possible to
insert, on the bay level in the plant structure, according to the installed connectivity package.
Section 4
1MRK 511 284-UEN B
Setting up a project
30
650 series
Engineering manual
© Copyright 2013 ABB. All rights reserved