IEC08000415.vsd
Station
IEC08000415 V1 EN-US
Figure 64: IEC 61850: Export SCD step 1
2.
Right-click the station and select
Export ....
3.
Select a location from the open standard Windows menu to store the file and name it.
4. The
SCL Export Options window opens, see
IEC09000627-1-en.vsd
IEC09000627 V1 EN-US
Figure 65: IEC 61850: SCL Export Options
5. Select
Export Private Sections and click Export to export the private sections to the SCD
file. A progress window shows the ongoing export of the station.
7.3.2
Exporting ICD or CID files
GUID-4F25EC7C-D0E7-4B61-8507-34E1CDC152DF v2
Procedure to select the export type, when the IED is selected in the plant structure:
1.
Right-click the IED in the plant structure and select
Export to open the Export window.
2.
Select the type of file to export from the
Save as type drop down list.
•
Configured IED Description (*.cid) for the IEC 61850 structure as needed for the IED
at runtime.
•
IED Capability Description (*.icd) for the IEC 61850 structure, see
IEC08000416.vsd
IEC08000416 V1 EN-US
Figure 66: IEC 61850: Export IED file type selection
3.
The
SCL Export Options window opens.
4. Select
Export Private Sections, Export As SCL Template or Include Goose Sending IEDs and
click
Export, see
. Note that the options in
SCL Export Options window according
to
is only available when an ICD file is exported.
Section 7
1MRK 511 284-UEN B
IEC 61850 communication engineering
80
650 series
Engineering manual
© Copyright 2013 ABB. All rights reserved