IEC08000418.vsd
IEC08000418 V1 EN-US
Figure 67: IEC 61850: Export IED file Options
7.4
Engineering of vertical and horizontal communication
in IET600
GUID-04ED1306-BAE6-49D2-8C84-11849EACC711 v7
For IEC 61850 engineering a separate system configuration tool is needed to be used with
PCM600. In PCM600 Ver. 2.3 or earlier the recommended tool is CCT600. In PCM600 Ver. 2.4 or
later the recommended tool is IET600, which is also included in the PCM600 Engineering Pro
installation package. In PCM600 Ver. 2.5, a lot of engineering described below can be done in
the PCM directly.
Procedure for signal engineering for the station by using IET600:
1.
Create a project in IET600.
2.
Import the SCD file exported from PCM600.
All data sets, report control blocks and GOOSE control blocks must be
located at LD0/LLN0. Due to IED capability, there are limitations regarding
the maximum number of data sets, number of entries in a data set and the
number of report control blocks that can be used.
3.
Add and/or reconfigure default data sets. The 650 series configured IED includes a
number of predefined data sets, but it is possible to add additional data sets and/or
reconfigure default data sets according to the requirements.
Note that reporting data sets shall only contain data intended to be used
by clients, for example for event handling.
4. Configure report control blocks for each data set used for vertical communication. The
650 series configured IED includes a number of predefined report control blocks, but it is
possible to add additional control blocks and/or reconfigure default control blocks
according to the requirements.
Up to 8 report clients can be configured.
5. Connect the report control blocks to vertical IED clients. The report control blocks are
connected to the vertical clients in the SCD file for a 650 series pre-configured IED. Check
each IED client and configure them to the subnetwork before connecting report control
blocks to the clients.
6. Create a GOOSE message data set for the sending IED. Define the content of the data set
according to the requirements.
1MRK 511 284-UEN B
Section 7
IEC 61850 communication engineering
650 series
81
Engineering manual
© Copyright 2013 ABB. All rights reserved