The inverse time delay is defined as:
0
0
inv
0
0
kSN (3I 3U cos (reference))
t
3I 3U cos (measured)
×
×
×
j
=
×
×
j
EQUATION1942 V2 EN
(Equation 55)
8.3.7.4
Directional residual current protection measuring 3I
0
and φ
The function will operate if the residual current is larger that the set value and the angle
φ = ang(3I
0
)-ang(U
ref
= -3U
0
) is within the sector
RCADir
±
ROADir
-3U
0
Operate area
3I
0
RCADir
= 0º
ROADir
= 80º
IEC06000652-3-en.vsd
IEC06000652 V3 EN
Figure 104:
Example of characteristic
For trip, the residual current 3I
0
shall be larger than the set level
INDir>
, the release
voltage 3U
0
shall be larger than the set level
UNREL>
and the angle φ shall be in the
set sector
ROADir
and
RCADir
.
When the function is activated binary output signals START and STDIRIN are
activated. If the output signals are active after the set delay
tDef
the binary output
signals TRIP and TRDIRIN are activated.
The function indicate forward/reverse direction to the fault. Reverse direction is
defined as φ is within the angle sector:
RCADir
+ 180° ±
ROADir
This sub-function has definite time delay.
Section 8
1MRK 502 048-UEN A
Current protection
210
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...