11.2.4
Signals
Table 204:
TCSSCBR Input signals
Name
Type
Default
Description
TCS_STATE
BOOLEAN
0
Trip circuit fail indication from I/O-card
BLOCK
BOOLEAN
0
Block of function
Table 205:
TCSSCBR Output signals
Name
Type
Description
ALARM
BOOLEAN
Trip circuit fault indication
11.2.5
Settings
Table 206:
TCSSCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
tDelay
0.020 - 300.000
s
0.001
3.000
Operate time delay
11.2.6
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of trip circuit supervision can be described by using a module diagram.
All the modules in the diagram are explained in the next sections.
GUID-9D3B79CB-7E06-4260-B55F-B7FA004CB2AC V1 EN
Figure 162:
Functional module diagram
Trip circuit supervision generates a current of approximately 1.0 mA
through the supervised circuit. It must be ensured that this current will
not cause a latch up of the controlled object.
1MRK 502 048-UEN A
Section 11
Secondary system supervision
319
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...