14.17.8
Technical data
Table 432:
SSCBR Technical data
Function
Range or value
Accuracy
Alarm levels for open and close
travel time
(0-200) ms
± 0.5% ± 25 ms
Alarm levels for number of
operations
(0 - 9999)
-
Setting of alarm for spring
charging time
(0.00-60.00) s
± 0.5% ± 25 ms
Time delay for gas pressure
alarm
(0.00-60.00) s
± 0.5% ± 25 ms
Time delay for gas pressure
lockout
(0.00-60.00) s
± 0.5% ± 25 ms
14.18
Measurands for IEC 60870-5-103 I103MEAS
14.18.1
Functionality
103MEAS is a function block that reports all valid measuring types depending on
connected signals.
The measurand reporting interval set for MMXU function blocks, using the
xDbRepInt
and
xAngDbRepInt
settings, must be coordinated with the event reporting
interval set for the IEC 60870-5-103 communication using setting
CycMeasRepTime
.
1MRK 502 048-UEN A
Section 14
Monitoring
573
Technical manual