Signal
Description
IDIFF
Magnitude of fundamental frequency differential current
ANGLE
Direction angle from zero sequence feature
I2RATIO
Second harmonic ratio
6.2.5
Settings
Table 33:
Basic general settings for the function REFPDIF (REF1-)
Parameter
Range
Step
Default
Unit
Description
GlobalBaseSel
1 - 6
1
1
-
Selection of one of
the Global Base
Value groups
Table 34:
Basic parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
Step
Default
Unit
Description
Operation
Off
On
-
Off
-
Operation Off / On
IdMin
4.0 - 100.0
0.1
10.0
%IB
Maximum sensitivity
in % of IBase
Table 35:
Advanced parameter group settings for the function REFPDIF (REF1-)
Parameter
Range
Step
Default
Unit
Description
ROA
60 - 90
1
60
Deg
Relay operate angle
for zero sequence
directional feature
6.2.6
Monitored data
Table 36:
REFPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
IRES
REAL
-
A
Magnitude of
fundamental frequency
residual current
IN
REAL
-
A
Magnitude of
fundamental frequency
neutral current
IBIAS
REAL
-
A
Magnitude of the bias
current
IDIFF
REAL
-
A
Magnitude of
fundamental frequency
differential current
ANGLE
REAL
-
deg
Direction angle from zero
sequence feature
I2RATIO
REAL
-
-
Second harmonic ratio
1MRK 502 048-UEN A
Section 6
Differential protection
111
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...