The fuse supervision is connected to ULN1OK-ULN1FF, ULN2OK-ULN2FF and
with alternative Healthy or Failing MCB signals depending on what is available from
each MCB.
The tie circuit breaker is connected either to bus 1 or line 1 voltage on one side and the
other side is connected either to bus 2 or line 2 voltage. Four different output
combinations are possible, bus to bus, bus to line, line to bus and line to line.
•
The line 1 voltage is selected if the line 1 disconnector is closed.
•
The bus 1 voltage is selected if the line 1 disconnector is open and the bus 1 circuit
breaker is closed.
•
The line 2 voltage is selected if the line 2 disconnector is closed.
•
The bus 2 voltage is selected if the line 2 disconnector is open and the bus 2 circuit
breaker is closed.
The function also checks the fuse-failure signals for bus 1, bus 2, line 1 and line 2. If
a VT failure is detected in the selected voltage an output signal USELFAIL is set. This
output signal is true if the selected bus or line voltages have a MCB trip. This output
as well as the function can be blocked with the input signal BLOCK. The function
block diagram for the voltage selection of a bus circuit breaker is shown in figure
and for the tie circuit breaker in figure
.
Section 12
1MRK 502 048-UEN A
Control
334
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...