10.3.5
Settings
Table 196:
SAPFRC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
StartFreqGrad
-10.00 - 10.00
Hz/s
0.01
0.50
Frequency gradient start value, the sign
defines direction
tTrip
0.000 - 60.000
s
0.001
0.200
Operate time delay in positive / negative
frequency gradient mode
RestoreFreq
45.00 - 65.00
Hz
0.01
49.90
Restore is enabled if frequency is above
set frequency value
tRestore
0.000 - 60.000
s
0.001
0.000
Restore time delay
10.3.6
Operation principle
Rate-of-change frequency protection SAPFRC is used to detect fast power system
frequency changes at an early stage. It has a settable definite time delay.To avoid an
unwanted trip due to uncertain frequency measurement at low voltage magnitude, a
voltage controlled blocking of the function is available from the preprocessing
function that is, if the voltage is lower than the set blocking voltage in the
preprocessing function, the function is blocked and no START or TRIP signal is
issued. If the frequency recovers, after a frequency decrease, a restore signal is issued.
10.3.6.1
Measurement principle
The rate-of-change of the fundamental frequency of the selected voltage is measured
continuously, and compared with the set value
(StartFreqGrad)
. If the voltage
magnitude decreases below the setting
MinValFreqMeas
in the preprocessing
function, which is set as a percentage of a global base voltage parameter, SAPFRC is
blocked and the output BLKDMAGN is issued. The sign of the setting
StartFreqGrad
, controls if SAPFRC reacts on a positive or on a negative change in
frequency. If SAPFRC is used for decreasing frequency that is, the setting
StartFreqGrad
has been given a negative value, and a trip signal has been issued, a
100 ms pulse is issued on the RESTORE output, when the frequency recovers to a
value higher than the setting
RestoreFreq
. A positive setting of
StartFreqGrad
, sets
SAPFRC to START and TRIP for frequency increases.
To avoid oscillations of the output START signal, a hysteresis has been included.
10.3.6.2
Time delay
SAPFRC has a settable definite time delay,
tTrip
.
Trip signal issuing requires that SAPFRC condition continues for at least the user set
time delay,
tTrip
. If the START condition, ceases during the delay time and is not
Section 10
1MRK 502 048-UEN A
Frequency protection
304
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...