AND
BLOCK
TRIN
Operation Mode = On
OR
t
tTripMin
TRIP
en05000789.vsd
Program = 3Ph
IEC05000789 V1 EN
Figure 214:
Simplified logic diagram for three phase trip
Lockout can be activated either by activating the input (SETLKOUT) or
automatically from trip input by setting
AutoLock
to
On
. A Lockout condition will be
indicated by activation of the output (CLLKOUT). If lockout has been activated it can
be reset by activating the input (RSTLKOUT) or via the HMI.
If
TripLockout
is set to
On
an active Lockout will result in a three-phase trip output.
In this way if both
AutoLock
and
TripLockout
are set to
On
the trip will always be
three-phase and sealed in.
13.1.7
Technical data
Table 296:
SMPPTRC technical data
Function
Range or value
Accuracy
Trip action
3-ph
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
13.2
Trip matrix logic TMAGGIO
13.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic
TMAGGIO
-
-
13.2.2
Functionality
The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route
trip signals and other logical output signals to the tripping logics SMPPTRC and
SPTPTRC or to different output contacts on the IED.
1MRK 502 048-UEN A
Section 13
Logic
435
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...