Section 6
Differential protection
6.1
Transformer differential protection
6.1.1
Functionality
Transformer differential protection, three-winding T3WPDIF is provided with
internal CT ratio matching and vector group compensation and settable zero sequence
current elimination.
The function can be provided with -phase sets of current inputs. All current inputs are
provided with percentage bias restraint features, making the IED suitable for two- or
three-winding transformer arrangements.
Three-winding applications
xx05000052.vsd
IEC05000052 V1 EN
three-winding power
transformer with all
three windings
connected
xx05000049.vsd
IEC05000049 V1 EN
three-winding power
transformer with
unconnected delta
tertiary winding
Figure 29:
CT group arrangement
for differential
protection and other
protections
The setting facilities cover the application of the differential protection to all types of
power transformers and auto-transformers with or without load tap changer as well as
shunt reactors and local feeders within the station. An adaptive stabilizing feature is
included for heavy through-faults.
Stabilization is included for inrush and overexcitation currents respectively, cross-
blocking is also available. Adaptive stabilization is also included for system recovery
inrush and CT saturation during external faults. A high set unrestrained differential
current protection element is included for a very high speed tripping at a high internal
fault currents.
1MRK 502 048-UEN A
Section 6
Differential protection
81
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...