Name
Type
Default
Description
QC21_CL
BOOLEAN
0
Earthing switch QC21 on busbar WA2 is in closed
position
QC71_OP
BOOLEAN
0
Earthing switch QC71 on busbar WA7 is in open
position
QC71_CL
BOOLEAN
0
Earthing switch QC71 on busbar WA7 is in closed
position
BB7_D_OP
BOOLEAN
0
Disconnectors on busbar WA7 except in the own
bay are open
BC_12_CL
BOOLEAN
0
A bus coupler connection exists between busbar
WA1 and WA2
BC_17_OP
BOOLEAN
0
No bus coupler connection exists between busbar
WA1 and WA7
BC_17_CL
BOOLEAN
0
A bus coupler connection exists between busbar
WA1 and WA7
BC_27_OP
BOOLEAN
0
No bus coupler connection exists between busbar
WA2 and WA7
BC_27_CL
BOOLEAN
0
A bus coupler connection exists between busbar
WA2 and WA7
VOLT_OFF
BOOLEAN
0
There is no voltage on the line and not VT (fuse)
failure
VOLT_ON
BOOLEAN
0
There is voltage on the line or there is a VT (fuse)
failure
VP_BB7_D
BOOLEAN
0
Switch status of the disconnectors on busbar WA7
are valid
VP_BC_12
BOOLEAN
0
Status of the bus coupler apparatuses between
WA1 and WA2 are valid
VP_BC_17
BOOLEAN
0
Status of the bus coupler apparatuses between
WA1 and WA7 are valid
VP_BC_27
BOOLEAN
0
Status of the bus coupler apparatus between WA2
and WA7 are valid
EXDU_ES
BOOLEAN
0
No transmission error from any bay containing
earthing switches
EXDU_BPB
BOOLEAN
0
No transmission error from any bay with
disconnectors on WA7
EXDU_BC
BOOLEAN
0
No transmission error from any bus coupler bay
QB9_EX1
BOOLEAN
0
External condition for apparatus QB9
QB9_EX2
BOOLEAN
0
External condition for apparatus QB9
QB1_EX1
BOOLEAN
0
External condition for apparatus QB1
QB1_EX2
BOOLEAN
0
External condition for apparatus QB1
QB1_EX3
BOOLEAN
0
External condition for apparatus QB1
QB2_EX1
BOOLEAN
0
External condition for apparatus QB2
QB2_EX2
BOOLEAN
0
External condition for apparatus QB2
QB2_EX3
BOOLEAN
0
External condition for apparatus QB2
QB7_EX1
BOOLEAN
0
External condition for apparatus QB7
QB7_EX2
BOOLEAN
0
External condition for apparatus QB7
QB7_EX3
BOOLEAN
0
External condition for apparatus QB7
QB7_EX4
BOOLEAN
0
External condition for apparatus QB7
1MRK 502 048-UEN A
Section 12
Control
403
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...