8.4.6
Monitored data
Table 106:
TRPTTR Monitored data
Name
Type
Values (Range)
Unit
Description
TTRIP
REAL
-
-
Estimated time to trip (in
min)
TTRIPCAL
INTEGER
-
-
Calculated time status to
trip: not active/long time/
active
TRESCAL
INTEGER
-
-
Calculated time status to
reset: not active/long
time/active
TRESLO
REAL
-
-
Estimated time to reset of
the function (in min)
HEATCONT
REAL
-
%
Percentage of the heat
content of the
transformer
I-MEASUR
REAL
-
%
Current measured by the
function in % of the rated
current
8.4.7
Operation principle
The sampled analogue phase currents are pre-processed and for each phase current the
true RMS value of each phase current is derived. These phase current values are fed
to the Thermal overload protection, two time constants (TRPTTR).
From the largest of the three phase currents a relative final temperature (heat content)
is calculated according to the expression:
2
final
ref
I
I
æ
ö
Q
= ç
÷
ç
÷
è
ø
EQUATION1171 V1 EN
(Equation 56)
where:
I
is the largest phase current
I
ref
is a given reference current
If this calculated relative temperature is larger than the relative temperature level
corresponding to the set operate (trip) current a start output signal START is activated.
The actual temperature at the actual execution cycle is calculated as:
1MRK 502 048-UEN A
Section 8
Current protection
217
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...