Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
System component for parallel
redundancy protocol
PRPSTATUS
-
-
16.10.1
Functionality
Redundant station bus communication according to IEC 62439-3 Edition 2 is
available as option in the Customized 650 Ver 1.3 series IEDs, and the selection is
made at ordering. Redundant station bus communication according to IEC 62439-3
Edition 2 uses both ports LAN1A and LAN1B on the COM03 module.
Select COM03 for redundant station bus according to IEC 62439-3
Edition 2 protocol, at the time of ordering.
IEC 62439-3 Edition 2 is NOT compatible with IEC 62439-3 Edition
1.
16.10.2
Principle of operation
The redundant station bus communication is configured using the local HMI,
Main
Menu/Configuration/Communication/TCP-IP configuation/ETHLAN1_AB
.
The settings are also visible in PST in PCM600.
The communication is performed in parallel, that is the same data package is
transmitted on both channels simultaneously. The received package identity from one
channel is compared with the data package identity from the other channel. If the
identity is the same, the last package is discarded.
PRPSTATUS supervises redundant communication on the two channels. If no data
package has been received on one or both channels within the last 10 s, the output
LAN1-A and/or LAN1-B are set to indicate error.
1MRK 502 048-UEN A
Section 16
Station communication
611
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...