Electrical installation 61
DC PV quick connector assembly (-SX)
WARNING!
Do not do electrical work on the unit unless you are a qualified
electrician. Obey the instructions in Chapter
on page
. Failure to obey
the safety instructions can cause injury or death, electromagnetic interference and
equipment malfunction.
To disassemble the PV quick connector, refer to the manufacturer’s documentation.
To assemble the PV quick connector:
1. Make sure that the DC cables are isolated from power. Refer to
on page
2. Use Phoenix Contact SUNCLIX connectors. Make sure that the cables are of the correct
type and diameter. Refer to www.phoenixcontact.com for more information.
Connector type
Cable cross
section
Cable outer
diameter
Rated current
IEC (90 °C)
DC+
: PV-CF-S (1774674)
DC-
: PV-CM-S (1774687)
2.5…6.0 mm
2
5.0…8.0 mm 27 A (2.5 mm
2
)
40 A (4.0…6.0 mm
2
)
3. Remove 15 mm of the insulation to
expose the conductor.
4. Install the conductor into the spring
cage contact of the connector.
Make sure that the conductor is
fully in the connector.
5. Fully close the spring.
6. Install the cable gland over the
spring cage contact.
7. Tighten the cable gland to 2 N·m.
15mm
4
5
6
7
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Hardware description ...
Page 40: ...40 Installation requirements ...
Page 70: ...70 Electrical installation ...
Page 74: ...74 Installation checklist ...
Page 110: ...110 Maintenance ...
Page 134: ...134 Navigation map The navigation map ...
Page 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...