Technical data 125
Output side
Inverter type
PRO-33.0-TL-OUTD-[-/S/SX]-400
AC grid connection type
Three phase 3W + PE or 4W + PE
Rated AC power (
P
AC, R
, @cos >0.99)
33,000 W
Maximum apparent power (S
max
)
33,000 VA
Rated AC grid voltage (V
AC, R
)
400 V
AC voltage range
320
…
480 V
Range varies according to the country grid standard.
Rated AC output current (
I
AC, R
)
47.8 A
Maximum AC output current (
I
AC, max
)
50.3 A
Rated output frequency (
f
R
)
50 Hz / 60 Hz
Output frequency range (f
min
…
f
max
)
47
…
53 Hz / 57
…
63 Hz
Range varies according to the country grid standard.
Nominal power factor and adjustable
range
>0.995, with Pacr = 33.0 kW, adj. ±0.9 with Pacr =
29.7 kW, adj. ±0
…
1 with S = 33.0 kVA
PQ diagram, with
- Over 95
…
110% of the nominal grid voltage
- The DC voltage is over 580
…
850 V
- The temperature is under 40 °C
Total current harmonic distortion
< 3%
AC connector type
Fixed plug, 4-pole + PE
AC connector ratings
Conductor cross section 10
…
25 mm
2
Cable diameter 22
…
32 mm (14...26 mm with reducer
seal)
Maximum current 125 A
Maximum voltage 630 V
AC
36
33
30
27
24
21
18
15
12
9
6
3
0
-3
-6
-9
-12
-15
-18
-21
-24
-27
-30
-33
-36
36
33
30
27
24
21
18
15
12
9
6
3
0
PQ Diagram
Reactive Power (kVAr)
Active Power (kW)
Active Power (kW)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Hardware description ...
Page 40: ...40 Installation requirements ...
Page 70: ...70 Electrical installation ...
Page 74: ...74 Installation checklist ...
Page 110: ...110 Maintenance ...
Page 134: ...134 Navigation map The navigation map ...
Page 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...