Start-up 81
Comm control
Commits the changes in the EFB
settings or activates the silent mode.
Enabled
Normal operation.
Refresh settings
Commits the modified EFB settings.
Reverts automatically to
Enabled
.
Silent mode
Activates the silent mode (no
messages are transmitted).
The silent mode can be canceled
with the
Refresh settings
item.
Comm diagnostics
Bit positions:
Status of the EFB communication.
Read-only parameter.
0 – Init failed
1 = EFB initialization failed
1 – Addr config err
1 = Node address not allowed by
protocol
2 – Silent mode
1 = Inverter not allowed to transmit
0 = Inverter allowed to transmit
3 – Autobauding
1 = Inverter attempting to determine
transfer rate
4 – Wiring error
1 = Errors detected (Data+/Data-
wires possibly swapped)
5 – Parity error
1 = Error detected: Check the
Baud
rate
and
Parity
parameters.
6 – Baud rate error
1 = Error detected: Check the
Baud
rate
and
Parity
parameters.
7 – No bus activity
1 = 0 bytes received in last 5
seconds.
8 – No packets
1 = 0 packets (addressed to any
device) detected in last 5 seconds.
9 – Noise or addressing
error
1 = Errors detected: Interference or
another device online with the same
address.
10 – Comm loss
1 = 0 packets addressed to the
inverter received within timeout.
11 – CW/Ref loss
1 = No control word or references
received within timeout.
12 – Not active
Reserved.
13 – Protocol 1
1 = Protocol-dependent status
information.
14 – Protocol 2
1 = Protocol-dependent status
information.
15 – Internal error
1 = Problem with the calls to the
inverter control program.
To set up the remote monitoring interface:
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Hardware description ...
Page 40: ...40 Installation requirements ...
Page 70: ...70 Electrical installation ...
Page 74: ...74 Installation checklist ...
Page 110: ...110 Maintenance ...
Page 134: ...134 Navigation map The navigation map ...
Page 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...