80 Start-up
Remote monitoring setup
To set up the remote monitoring interface:
From
Menu
->
Communication
->
Embedded
Fieldbus
Set parameters:
To change parameter values:
1. Do the changes to a parameter.
2. Select the
Comm control
parameter.
3. Select
Refresh settings
.
Parameter
Values
Description
Protocol enable
Enables/disables the embedded
fieldbus interface and selects the
protocol to use.
None
No communication.
Modbus RTU
(default)
EFB is enabled and it uses the
Modbus RTU protocol.
Node address
1…247
(default: 1)
Node address of the inverter. All
devices must have different
addresses.
Baud rate
Sets the data transfer rate.
Autodetect
The inverter automatically sets the
transfer rate after monitoring traffic.
Note: Set the Parity parameter
before you enable autodetection.
9.6 kbps, 19.2 kbps,
38.4 kbps, 57.6 kbps,
76.8 kbps, 115.2 kbps
The default value is 19.2 kbps.
Parity
Sets the number of data bits, the
type of the parity bit and the number
of stop bits.
8 NONE 1
(default)
8 data bits, no parity bit, 1 stop bit
8 NONE 2
8 data bits, no parity bit, 2 stop bits
8 EVEN 1
8 data bits, even parity bit, 1 stop bit
8 ODD 1
8 data bits, odd parity bit, 1 stop bit
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Hardware description ...
Page 40: ...40 Installation requirements ...
Page 70: ...70 Electrical installation ...
Page 74: ...74 Installation checklist ...
Page 110: ...110 Maintenance ...
Page 134: ...134 Navigation map The navigation map ...
Page 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...