Technical data 129
Derating
The inverter monitors its internal temperature and derates the power output when
necessary to prevent damage to the inverter, protection devices and cabling. If the
temperature of the inverter rises or the operational currents are too high, the inverter
disconnects from the electrical grid and gives the overtemperature fault. When the
internal temperature decreases, the inverter connects to the grid again.
The nominal output power can be achieved in ambient temperatures of up to 45 °C
(113 °F) in the whole MPP operating voltage range. At the minimum MPP voltage
580 V
DC
, the nominal output power can be achieved even at 50 °C (122 °F). In the
ambient temperature range of 45…60 °C (113…140 °F), the output power is derated.
The power derating curves are applicable up to 1,000 m (3280 ft) above sea level. If
the inverter is installed above 1,000 m, the cooling capacity is reduced due to the
thinner air. The inverter temperature management attempts to compensate for the
reduced cooling. The power derating can start at temperatures lower than those
mentioned above.
Active power vs. temperature at power factor = 1:
580 Vdc
850 Vdc
950 Vdc
60
55
50
45
40
35
30
25
20
15
10
5
0
-5
-10
-15
-20
-25
35
30
25
20
15
10
5
0
P
max
(T) at PF=1
Ambient temperature (°C)
Maximum
Active Power (kW)
Summary of Contents for PRO-33.0-TL Series
Page 1: ...ABB solar inverters Product manual PRO 33 0 TL string inverters ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 32: ...32 Hardware description ...
Page 40: ...40 Installation requirements ...
Page 70: ...70 Electrical installation ...
Page 74: ...74 Installation checklist ...
Page 110: ...110 Maintenance ...
Page 134: ...134 Navigation map The navigation map ...
Page 136: ...Contact us www abb com solarinverters 3AUA0000123261 Rev B EN 2015 06 18 ...