ABB i-bus® KNX
GROUP OBJECTS
Function
Group object name
Data point
type
Length
Flags
Controller Status HVAC (master)
Channel X – Controller
DPT 5.001
1 byte
C R
T
This group object sends the following status information on the bus (ABB i-bus® KNX):
•
Operating mode
Heating
/
cooling
•
Operation
active
/
inactive
•
Status Frost and dew point alarm
•
Operating mode
Note
If a slave is used:
This group object must be connected to the corresponding group object of the slave to ensure the functionality of master/slave operation.
Prerequisites for visibility
•
\ Option
Controller channel
Current HVAC operating mode
Channel X – Controller
DPT 20.102
1 byte
C R
T
This group object sends the HVAC operating mode on the bus (ABB i-bus® KNX) after evaluation of all priorities and influences.
Telegram value:
•
1 = Comfort
•
2 = Standby
•
3 = Economy
•
4 = Building Protection
Prerequisites for visibility
•
\ Option
Controller channel
Comfort heating setpoint
Channel X – Controller
DPT 9.001
2 bytes
C
W
This group object is used to receive a setpoint adjustment for the operating mode
Comfort heating
via the bus (ABB i-bus® KNX).
This group object overrides the value set in the parameter
. The overridden setpoint is limited to the valid value range (10 … 40 °C).
Manual setpoint adjustment acts on the overridden setpoint.
Telegram value:
•
10 … 40 °C
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage heating [controller]
all options except
Deactivated
•
Setpoint specification and adjustment
\ Option
Absolute
Setpoint Comfort heating/cooling
Channel X – Controller
DPT 9.001
2 bytes
C
W
This group object is used to receive a setpoint adjustment for the operating mode
Comfort heating/cooling
via the bus (ABB i-bus® KNX).
This group object overrides the value set in the parameter
Comfort heating and cooling setpoint
. The overridden setpoint is limited to the valid value range
(10 … 40 °C).
Manual setpoint adjustment acts on the overridden setpoint.
Telegram value:
•
10 … 40 °C
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage heating [controller]
all options except
Deactivated
–
Basic-stage cooling [controller]
\
all options except
Deactivated
•
–
Comfort heating setpoint = Comfort cooling setpoint
\
Option
Yes
–
Setpoint specification and adjustment
\
Option
Absolute
Comfort cooling setpoint
Channel X – Controller
DPT 9.001
2 bytes
C
W
This group object is used to receive a setpoint adjustment for the operating mode
Comfort cooling
via the bus (ABB i-bus® KNX).
This group object overrides the value set in the parameter
. The overridden setpoint is limited to the valid value range (10 … 40 °C).
Manual setpoint adjustment acts on the overridden setpoint.
Telegram value:
•
10 … 40 °C
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage cooling [controller]
\
all options except
Deactivated
•
Setpoint specification and adjustment
\ Option
Absolute
Economy heating setpoint
Channel X – Controller
DPT 9.001
2 bytes
C
W
This group object is used to receive a setpoint adjustment for the operating mode
Economy heating
via the bus (ABB i-bus® KNX).
This group object overrides the value set in the parameter
. The overridden setpoint is limited to the valid value range (10…40 °C) and
limited by the value
Comfort heating
.
Manual setpoint adjustment acts on the overridden setpoint.
Telegram value:
•
10 … 40 °C
Prerequisites for visibility
•
–
Option
Controller channel
–
Basic-stage heating [controller]
all options except
Deactivated
•
–
Option
Comfort, Standby, Economy, Building Protection
–
Setpoint specification and adjustment
\
Option
Absolute
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B