ABB i-bus® KNX
PARAMETERS
Heating
Cooling
Actual temperature > (se hysteresis/upper
switching point)
Controller Off
Controller On
Actual temperature < (setpoint – hysteresis/lower
switching point)
Controller On
Controller Off
Tab. 20: Dependency of hysteresis on the operating mode
Option
0.3 … 0.5 … 25.5 K
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Type of control value Basic-stage heating
Options
2-point 1 bit (On/Off) / 2-point
1 byte (0/100 %)
– Parameter
Option
Yes
• The parameter is in the parameter window
parameter window
.
or
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
all options except
Deactivated
– Parameter
Type of control value Additional-stage heating
Options
2-point 1 bit (On/Off) / 2-point
1 byte (0/100 %)
– Parameter
Option
Yes
• The parameter is in the parameter window
parameter window
or
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage cooling [controller]
all options except
Deactivated
– Parameter
Type of control value Basic-stage cooling
\
Options
2-point 1 bit (On/Off) / 2-point 1
byte (0/100 %)
– Parameter
Option
Yes
• The parameter is in the parameter window
parameter window
or
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage cooling [controller]
all options except
Deactivated
– Parameter
all options except
Deactivated
– Parameter
Type of control value Additional-stage cooling
\
Options
2-point 1 bit (On/Off) / 2-point
1 byte (0/100 %)
– Parameter
Option
Yes
• The parameter is in the parameter window
parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
87