ABB i-bus® KNX
PARAMETERS
7.4.61
I-proportion at temperature limitation
This parameter is used to define what happens with the I-proportion when the limit temperature is
reached.
More information: →
Basics of PI control, Page 178
.
Option
Freeze
The current value of the I-proportion is saved. When the controller becomes active again, the saved
value is used for control.
Reset
The I-proportion is reset to 0. When the controller becomes active, the I-proportion starts at 0.