ABB i-bus® KNX
PARAMETERS
More information: →
Telegram rate limit, Page 189
.
Option
1 … 20 … 50
Prerequisites for visibility
\ Option
Yes
• The parameter is in the parameter window
.
7.4.78
Maximum setpoint increase
This parameter is used to define the permissible value of the maximum setpoint increase via the analog
room control unit. The setpoint adjustment only applies to the
Comfort operating mode.
Note
Beginning from the center position of the rotary knob, the temperature value set is distributed over
the range in the clockwise direction. The right stop of the rotary knob corresponds to the maximum
value set (e.g. 3 K).
Option
0 … 3 … 5 K
Prerequisites for visibility
\ Parameter
room control unit to physical device input a
\ Option
Yes
• The parameter is in the parameter window
7.4.79
Maximum setpoint reduction
This parameter is used to define the permissible value of the maximum setpoint reduction via the analog
room control unit. The setpoint adjustment only applies to the
Comfort operating mode.
Note
Beginning from the center position of the rotary knob, the temperature value set is distributed over
the range in the counterclockwise direction. The left stop of the rotary knob corresponds to the maxi-
mum value set (e.g. 3 K).
Option
0 … 3 … 5 K
Prerequisites for visibility
\ Parameter
room control unit to physical device input a
\ Option
Yes
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
99