ABB i-bus® KNX
GROUP OBJECTS
Function
Group object name
Data point
type
Length
Flags
Reset manual setpoint adjustment
Setpoint Comfort heating/cooling
Status Control value additional-stage cooling
Status Control value additional-stage cooling
Status Control value additional-stage heating
Status Control value additional-stage heating
Status Control value basic-stage cooling
Status Control value basic-stage cooling
Status Control value basic-stage heating
Status Control value basic-stage heating
Summer compensation active/inactive
8.2
Group objects, general
Function
Group object name
Data point
type
Length
Flags
In operation
General
DPT 1.002
1 bit
C R
T
This group object cyclically sends an In operation telegram on the bus (ABB i-bus® KNX). The sending cycle is set in parameter
The telegram value depends on the setting in the parameter
Send value group object "In operation"
Telegram value:
•
1 = Device in operation
•
0 = Device in operation
Note
Readiness can be monitored by another KNX device using this group object. If a telegram is not received, the sending device could be faulty or the bus cable to the
transmitting device could be interrupted.
Prerequisites for visibility
•
Enable group object "In operation"
\ Option
Yes
Request status values
General
DPT 1.017
1 bit
C
W
If a telegram is received on this group object, the values of the status group objects are sent on the bus (ABB i-bus® KNX).
Telegram value:
•
1 = Send status values
•
0 = Send status values
Note
The values of the status group objects are sent only if sending on request is set in the related parameters.
Prerequisites for visibility
•
This group object is always visible.
Enable/block manual operation
General
DPT 1.003
1 bit
C
W
The
Manual operation
mode is enabled/blocked using this group object.
If
Manual operation
mode is active, it will be ended and blocked with telegram value 0.
Telegram value:
•
1 = Enable manual operation
•
0 = End manual operation and block
Prerequisites for visibility
•
\ Parameter
\ Option
Enabled
Status Manual operation
General
DPT 1.011
1 bit
C R
T
This group object sends the status of the
Manual operation
mode on the bus (ABB i-bus® KNX).
Telegram value:
•
1 = Manual operation active
•
0 = Manual operation inactive
Prerequisites for visibility
•
\ Parameter
\ Option
Enabled
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B