ABB i-bus® KNX
GROUP OBJECTS
Function
Group object name
Data point
type
Length
Flags
Error Input
Channel X – Input x
DPT 1.005
1 bit
C R
T
This group object monitors receipt of a temperature value at the input and sends a message on the bus (ABB i-bus® KNX).
Telegram value:
•
1 = Error
•
0 = No error
Prerequisites for visibility
•
Connect analog room control unit to physical device input a
\ Option
Yes
or
•
\ Parameter
\ Option
Temperature sensor
Window contact
Channel X – Input x
DPT 1.005
1 bit
C R
T
This group object sends the contact position of the connected sensor on the bus (ABB i-bus® KNX).
The send behavior depends on the setting in the parameter
Send status values [window contact]
.
Telegram value:
•
Depends on the setting in the parameter
Note
If an analog room control unit is connected to device input a, this group object is not available for device input a, →
Connect analog room control unit to physical
Prerequisites for visibility
•
\ Parameter
\ Option
Window contact
Fill level alarm
Channel X – Input x
DPT 1.005
1 bit
C R
T
This group object sends the contact position of the connected sensor on the bus (ABB i-bus® KNX).
The send behavior depends on the setting in the parameter
Send status values [fill level alarm]
.
Telegram value:
•
Depends on the setting in the parameter
Fill level reached if [input x]
Note
If an analog room control unit is connected to device input a, this group object is not available for device input a, →
Connect analog room control unit to physical
Prerequisites for visibility
•
\ Parameter
\ Option
Fill level sensor
Contact position binary input
Channel X – Input x
DPT 1.001
1 bit
C R
T
This group object sends the contact position of the sensor connected to the binary input on the bus (ABB i-bus® KNX).
Telegram value:
•
Depends on the setting in the following parameters:
–
Distinction between long and short operation
–
Note
If an analog room control unit is connected to device input a, this group object is not available for device input a, →
Connect analog room control unit to physical
Prerequisites for visibility
•
\ Parameter
\ Option
Binary input
Dew point alarm
Channel X – Input x
DPT 1.005
1 bit
C R
T
This group object sends the contact position of the connected sensor on the bus (ABB i-bus® KNX).
The send behavior depends on the setting in the parameter
Send status values [dew point alarm]
Telegram value:
•
Depends on the setting in the parameter
Dew point reached if [input x]
Note
If an analog room control unit is connected to device input a, this group object is not available for device input a, →
Connect analog room control unit to physical
Prerequisites for visibility
•
\ Parameter
\ Option
Dew point sensor
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
156
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page