Setpoint specification and adjustment
This parameter is used to define whether the setpoints are entered as absolute values or as differences
from the respective Comfort values.
Note
To ensure the correct function of the control and to obtain energy savings, there must be a logical rela-
tionship between the selected values of the individual operating modes.
• Comfort heating setpoint > Standby heating setpoint > Economy heating setpoint > Frost protec-
tion setpoint (Building Protection heating)
• Comfort cooling setpoint < Standby cooling setpoint < Economy cooling setpoint < Heat protection
setpoint (Building Protection cooling)
Option
Absolute
The setpoints for
Standby
and
Economy
modes are entered as absolute values.
The setpoints are mutually independent and are not shifted with the base setpoint.
The setpoints can be adjusted via the related group objects.
The following dependent parameters are shown:
•
•
•
•
The following dependent group objects are displayed:
•
•
•
•
Building Protection heating setpoint
•
•
•
•
Building Protection cooling setpoint
Relative
The setpoints for
Standby
and
Economy
modes are entered as values relative to the respective
Comfort values.
The setpoint temperatures are adjusted for all operating modes via the bus (ABB i-bus® KNX) using
group object
. The values for the
Building Protection
operating mode cannot be
changed via the bus (ABB i-bus® KNX).
The following dependent parameters are shown:
•
•
•
•
•
The following dependent group objects are displayed:
•
Prerequisites for visibility
\ Option
Controller channel
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
117
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page