ABB i-bus® KNX
PARAMETERS
7.4
Parameter descriptions
7.4.1
Economy heating reduction
This parameter is used to define the value by which the temperature is to be reduced in the
Economy
heating operating mode. The value is specified as a difference from the parameter
More information: →
Explanation of the operating modes, Page 174
Note
The controller ensures that the setpoint temperature is not exceeded when the actual temperature in-
creases. The operating mode is not changed.
Option
0 … 4 … 15 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Option
Comfort, Standby, Economy, Building Protection
– Parameter
Setpoint specification and adjustment
Option
Relative
• The parameter is in the parameter window
7.4.2
Standby heating reduction
This parameter is used to define the value by which the temperature is to be reduced in the
Standby
heating operating mode. The value is specified as a difference from the parameter
More information: →
Explanation of the operating modes, Page 174
Note
The controller ensures that the setpoint temperature is not exceeded when the actual temperature in-
creases. The operating mode is not changed.
Option
0 … 2 … 15 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Options
Comfort, Standby, Economy, Building Protection / Comfort,
Standby, Building Protection
– Parameter
Setpoint specification and adjustment
Option
Relative
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
54
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page