PARAMETERS
7.4.102
Comfort cooling setpoint
This parameter is used to define the setpoint temperature for the
Comfort cooling operating mode.
More information: →
Explanation of the operating modes, Page 174
Note
The temperature value specified here must be lower than the value in the parameter
. A difference of at least 2 K is recommended.
Option
10 … 25 … 40 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage cooling [controller]
all options except
Deactivated
\ Parameter
setpoint = Comfort cooling setpoint
\ Option
No
• The parameter is in the parameter window
7.4.103
Standby cooling setpoint
This parameter is used to define the setpoint temperature for the
Standby cooling operating mode.
More information: →
Explanation of the operating modes, Page 174
Note
The temperature value specified here must be higher than the value in the parameters
Comfort heating and cooling setpoint
. A difference of at least 2 K is recommended.
Note
The controller ensures that the setpoint temperature is not fallen below when the actual temperature
decreases. The operating mode is not changed.
Option
10 … 27 … 40 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Options
Comfort, Standby, Economy, Building Protection / Comfort,
Standby, Building Protection
– Parameter
Setpoint specification and adjustment
Option
Absolute
• The parameter is in the parameter window