FMBT-21 configuration parameters – group C (group 3)
Note: The actual parameter group number depends on the drive type. Group C (group
3) corresponds to:
•
parameter group 52 in ACS480, ACS580, ACH580 and ACQ580.
•
parameter group is typically 52/55 (group 152/155 in some variants) in ACS880 if
the adapter is installed as fieldbus adapter A/B.
Default
Description
Name/Value
No.
1)
0 = None
Selects the drive parameter address from which the data is read
to the Data in 1 register is written (from the server to the client).
The Modbus register address maps are explained in chapter
Modbus/TCP – Communication protocol
The content is defined
by a decimal number in the range of 0 to 9999 as follows:
FBA A/B data
in1 (drive to cli-
ent)
01
Not used
0
Virtual address area of drive control. Not used
when the Modbus/TCP protocol is used.
1...99
Parameter area of the drive
101...9999
Not used
0 = None
Parameter index with format xxyy, where
101…9999
• xx is the parameter group number (1…99)
• yy is the parameter number index within that group (01…99).
Note: In ACS480, ACS580 and ACS880, choose Other to display a
list of mappable drive parameters.
0 = None
See parameter
01 FBA A/B data in 1.
Data in 2 … Data
in 12
02
12
1) The number of parameters in this group may vary by drive type and drive firmware.
■
Control locations
ABB drives can receive control information from multiple sources including digital
inputs, analog inputs, the drive control panel and a fieldbus adapter module. ABB
drives allow the user to separately determine the source for each type of control
information (Start, Stop, Direction, Reference, Fault reset, etc.).
To give the fieldbus client the most complete control over the drive, you must select
the adapter module as the source of this information. The drive-specific parameter
setting examples below contain the drive control parameters relevant in the examples.
For a complete parameter list, see the drive documentation.
Starting up fieldbus communication for ACS480, ACx580
and ACS880 drives
1.
Power up the drive.
2.
Enable the communication between the adapter module and the drive by selecting
the correct slot number in parameter 50.01 FBA A enable.
Modbus/TCP – Start-up 33
12
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...