tables below and must be checked first and adjusted where necessary. You can adjust
the parameters via a drive control panel, a PC tool or a web user interface.
Note:
•
Not all drives display descriptive names for the configuration parameters.
•
The new parameter settings take effect only when you power up the module the
next time or when you activate the fieldbus adapter refresh parameter 51.27 FBA
A par refresh.
FMBT-21 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive type. Group A (group
1) corresponds to:
•
parameter group 51 in ACS380, ACS480, ACS580, ACH580 and ACQ580.
•
parameter group is typically 51/54 (group 151/154 in some variants) in ACS880 if
the adapter is installed as fieldbus adapter A/B.
Default
Description
Name/Value
No.
Mod-
bus/TCP
Read-only. Shows the fieldbus adapter type as detected by the
drive. The value cannot be adjusted by the user.
FBA type
01
If the value is 0 = None, the communication between the drive and
the module has not been established.
0 = MB/TCP
Selects the application protocol and communication profile for
the network connection.
Protocol/profile
02
ABB C
The selections available for Modbus communication are listed
below.
Modbus/TCP: ABB Drives profile - Classic
0 = MB/TCP ABB
C
Modbus/TCP: ABB Drives profile - Enhanced
1 = MB/TCP ABB
E
Modbus/TCP: Transparent 16-bit profile
2 = MB/TCP T16
Modbus/TCP: Transparent 32-bit profile
3 = MB/TCP T32
Modbus over UDP: ABB Drives profile - Classic
4 = MB/UDP
ABB C
Modbus over UDP: ABB Drives profile - Enhanced
5 = MB/UDP
ABB E
Modbus over UDP: Transparent 16-bit profile
6 = MB/UDP T16
Modbus over UDP: Transparent 32-bit profile
7 = MB/UDP T32
0 = Auto
Sets the bit rate for the Ethernet interface.
Commrate
03
Auto-negotiate
0 = Auto
100 Mbps, full duplex
1 = 100 Mbps FD
100 Mbps, half duplex
2 = 100 Mbps
HD
10 Mbps, full duplex
3 = 10 Mbps FD
10 Mbps, half duplex
4 = 10 Mbps HD
26 Modbus/TCP – Start-up
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...