Default
Description
Name/Value
No.
0 = Idle
or
4 = Offline
or
2 = Time out
Read-only. Displays the status of the fieldbus ad-
apter module communication.
Note: The value names may vary by drive.
D2FBA A/B comm
status
31
Adapter is not configured.
0 = Idle
Adapter is initializing.
1 = Exec.init
A timeout has occurred in the communication
between the adapter and the drive.
2= Time out
Adapter configuration error: The major or minor
revision code of the common program revision in
the fieldbus adapter module is not the revision re-
quired by the module or mapping file upload has
failed more than three times.
3= Conf.err
Adapter is off-line.
4 = Off-line
Adapter is on-line.
5 = On-line
Adapter is performing a hardware reset.
6 = Reset
N/A
Read-only. Displays patch and build numbers of
the adapter module's firmware version in xxyy
format, where:
FBA A/B comm SW
ver
32
xx = patch number
yy = build number.
Example: If the firmware version (<ma-
jor>.<minor>.<patch>.<build>) is 3.10.200.13, the
value C80D is displayed. If the version is 3.10.0.0,
the value 0 is displayed.
See also parameter 33.
N/A
Read-only. Displays major and minor revision
numbers of the adapter module's firmware version
in xxyy format, where:
FBA A/B appl SW ver
33
xx = major revision number
yy = minor revision number
Example: If the firmware version (<ma-
jor>.<minor>.<patch>.<build>) is 3.10.200.13 or
3.10.0.0, the value 310 is displayed.
See also parameter 32.
Starting up fieldbus communication
1.
Power up the drive.
2.
Enable communication between the adapter module and the drive by selecting
the correct slot number in parameter 50.01 FBA A enable.
The selection must correspond to the slot where the adapter module is installed.
For example, if the adapter module is installed in slot 1, you must select slot 1.
3.
Set the module configuration parameters in group 51.
•
select the communication protocol and profile with parameter 51.02, and
•
configure the network settings with parameters 51.03…51.13.
64 NONE – Start-up
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...