Modbus register
Input data
Modbus register
Output data
(4)00054
Output power [32]
(4)00004
Constant speed 1 [32]
1)
(4)00055
(4)00005
(4)00056
DC voltage [32]
(4)00006
Constant speed 2 [32]
(4)00007
(4)00057
1) Example
The table below gives the recommended drive parameter settings.
Description
Setting for ACS880 drives
Drive parameter
Enables communication between
the drive and the fieldbus adapter
module.
1 = Option slot 1
1)
50.01 FBA A enable
Enables fieldbus A communica-
tion fault monitoring.
1 = Fault
50.02 FBA A comm loss func
Defines the fieldbus A communic-
ation break supervision time.
3.0 s
50.03 FBA A comm loss t out
Selects the fieldbus A reference 1
type and scaling.
4 = Speed
50.04 FBA A ref1 type
Displays the type of the fieldbus
adapter module.
Modbus/TCP
2)
51.01 FBA A type
Selects the Modbus/TCP protocol
and the ABB Drives - Enhanced
profile.
1 = MB/TCP ABB E
51.02 Protocol/Profile
Ethernet communication rate is
negotiated automatically by the
device.
0 = Auto
51.03 Commrate
Configuration will be obtained
from parameters 05…13.
0 = Static IP
51.04 IP configuration
First part of the IP address
192
51.05 IP address 1
Second part of the IP address
51.06 IP address 2
Third part of the IP address
0
51.07 IP address 3
Last part of the IP address
51.08 IP address 4
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
24
51.09 Subnet CIDR
Sets the communication timeout
as 1 second.
10
51.20 Timeout time
The timeout feature monitors the
updating of the Control word and
Reference 1.
2 = Control RW
51.21 Timeout mode
Output power
01.14
52.01 FBA A data in1
DC voltage
01.11
52.03 FBA a data in3
Constant speed 1
22.26
53.01 FBA A data out1
Modbus/TCP – Start-up 37
12
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...