Default
Description
Name/Value
No.
Subnet mask in CIDR notation
1...31
0
IP gateways connect individual physical IP subnets into a unified
IP network. When an IP node needs to communicate with an IP
node on another subnet, the IP node sends the data to the IP
gateway for forwarding. Parameters 10…13 define the four octets
of the gateway address.
GW address 1
10
GW address
0...255
...
...
...
...
0
See parameter 10 GW address 1.
GW address 4
13
GW address
0…255
0 = Auto
Sets the bit rate for the Ethernet port 2.
Commrate port
2
14
Auto-negotiate
0 = Auto
100 Mbps, full duplex
1 = 100 Mbps FD
100 Mbps, half duplex
2 = 100 Mbps
HD
10 Mbps, full duplex
3 = 10 Mbps FD
10 Mbps, half duplex
4 = 10 Mbps HD
Disable services that are not required. Each service is represented
by a single bit. Bit 0, Lock configuration, can be used to prevent
accidental changing of this parameter. By default, all services are
enabled and configuration is unlocked.
Service configur-
ation
15
Information
Name
Bit
Changing this bit to one will lock service configuration and
no bit can be changed. Only resetting the fieldbus configura-
tion will unlock the parameter. To reset the fieldbus configur-
ation, choose "Reset all fieldbus settings" or "Clear all" in
parameter 96.06 Parameter restore.
Lock configuration
0
When this bit is set, access from ABB IP Configuration tool is
prevented.
Disable IP config tool
1
When this bit is set, access from Ethernet tool network (eg,
ABB Drive Composer tool) is prevented.
Disable ETH tool net-
work
2
When this bit is set, response to ICMP (ping) message is pre-
vented.
Disable ping response
3
When this bit is set, access from Ethernet tool network is un-
secured.
Note: Drive Composer pro before V2.7 supports unsecured
communication only.
Unsecured ETH tool
network
4
When this bit is set, access to web pages is disabled.
Disable configuring
web pages
5
Service configuration
0000b… 1111b
28 Modbus/TCP – Start-up
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...