Once communication between the drive and the adapter module is established, several
configuration parameters are copied to the drive. These parameters are shown in the
tables below and must be checked first and adjusted where necessary. You can adjust
the parameters via a drive control panel or a PC tool.
Note:
•
Not all drives will display the descriptive names for the configuration parameters.
•
The new parameter settings take effect only when you power up the module the
next time or when you activate the fieldbus adapter refresh parameter.
•
Use the NONE protocol selection when no fieldbus protocol is required. For
example, when only the Ethernet tool network is used or for synchronizing time.
FMBT-21 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive type. Group A (group
1) corresponds to:
•
parameter group 51 in ACS380, ACS480, ACH580, ACQ580 and ACS580.
•
parameter group 51 in ACS880 if the adapter is installed as fieldbus adapter A or
group 54 if the adapter is installed as fieldbus adapter B.
Default
Description
Name/Value
No.
Modbus/TCP
Read-only. Shows the fieldbus adapter type as de-
tected by the drive. The value cannot be adjusted
by the user.
FBA TYPE
01
If the value is 0 = None, the communication between
the drive and the module has not been established.
0=Modbus/TCP
Selects the application protocol and communication
profile for the network connection.
Protocol/Profile
02
The selections available for NONE protocol are lis-
ted below.
ABB Drives profile - Classic
0 = Modbus/TCP
NONE protocol
200 = NONE
0 = Auto
Sets the bit rate for the Ethernet interface.
Commrate
03
Autonegotiate
0 = Auto
100 Mbps, full duplex
1 = 100 Mbps FD
100 Mbps, half duplex
2 = 100 Mbps HD
10 Mbps, full duplex
3 = 10 Mbps FD
10 Mbps, half duplex
4 = 10 Mbps HD
1 = Dyn IP DHCP
Sets the method for configuring the IP address,
subnet mask and gateway address for the module.
IP configuration
04
Configuration is obtained from parameters 05…13.
0 = Static IP
Configuration is obtained via DHCP.
1 = Dyn IP DHCP
60 NONE – Start-up
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...