Default
Description
Name/Value
No.
0
IP gateways connect individual physical IP subnets
into a unified IP network. When an IP node needs
to communicate with an IP node on another subnet,
the IP node sends the data to the IP gateway for
forwarding. Parameters define the four octets of
the gateway address.
GW address 1
10
…
13
GW address
0...255
...
...
...
0
See parameter 10 GW address 1.
GW address 4
GW address
0.255
0 = Auto
Sets the bit rate for the Ethernet port 2.
Commrate port 2
14
Autonegotiate
0 = Auto
100 Mbps, full duplex
1 = 100 Mbps FD
100 Mbps, half duplex
2 = 100 Mbps HD
10 Mbps, full duplex
3 = 10 Mbps FD
10 Mbps, half duplex
4 = 10 Mbps HD
Disable services that are not required.
Service configuration
15
Each service is represented by a single bit. Bit 0,
Lock configuration, can be used to prevent accident-
al changing of this parameter.
By default, all services are enabled and configura-
tion is unlocked.
Information
Name
Bit
Changing this bit to one will lock service configuration and
no bit can be changed. Only resetting the fieldbus configura-
tion will unlock the parameter. To reset the fieldbus configur-
ation, choose "Reset all fieldbus settings" or "Clear all" in
parameter 96.06 Parameter restore.
Lock configuration
0
When this bit is set, access from ABB IP Configuration tool
is prevented.
Disable IP config tool
1
When this bit is set, access from Ethernet tool network (eg,
ABB Drive Composer tool) is prevented.
Disable ETH tool net-
work
2
When this bit is set, response to ICMP (ping) message is
prevented.
Disable ping response
3
When this bit is set, access from Ethernet tool network is
unsecured.
Note: Drive Composer pro before V2.7 supports unsecured
communication only.
Unsecured ETH tool
network
4
When this bit is set, access to web pages is disabled.
Disable configuring
web pages
5
Service configuration
0000b…1111b
62 NONE – Start-up
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...