Configuring SNTP
Simple Network Time Protocol (SNTP) can be used to synchronize drive time with a
network time server. When SNTP is enabled, FMBT-21 will request the time from
configured server at a given interval. To receive this time synchronization, you must
configure the drive with parameter 96.20 time sync primary source. The table below
shows the settings for SNTP:
Value
Description
Settings
Default: 30 seconds
Interval to request time from server.
SNTP update interval
Minimum: 30
seconds
-1440...1440
minutes
Time offset to the time received from SNTP.
This value can also be set over Modbus register
(4)00084.
SNTP time offset to UTC
Note: SNTP time offset change does not need a
reboot.
-
Primary server address for requesting time.
SNTP server address 1
Format: IP address followed by optional port num-
ber, eg:
192.168.0.1:123
Note: If port number is missing, the default NTP
port number "123" is used.
-
Secondary server address used if the request to
server 1 fails.
SNTP server address 2
■
Security page
On the Security page, you can upload a private key and certificates for FMBT-21 to use
instead of the self-signed certificate that FMBT-21 uses as a default. You can upload
and manage Drive Composer certificate files on Security page under "Drive Composer
certificate settings". Up to four certificates are supported at a time.
FMBT-21 uses secure HTTPS (TLS 1.2) communication for the web page server. By
default, FMBT-21 does not require client authentication for the PC tool communication.
You can use client authentication to improve the system security.
If unsecured communication is required, you can enable it from Service configuration
page or by setting parameter 51.15 Service configuration bit 4. When unsecured
communication is enabled, the PC tool communication is not encrypted or
authenticated.
For more details, refer to
Drive composer start-up and maintenance PC tool user's
manual (3AUA0000094606 [English])
.
Appendix D - FMBT-21 configuration web pages 87
Summary of Contents for FMBT-21
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 16: ...16 ...
Page 20: ...20 ...
Page 46: ...46 ...
Page 58: ...58 ...
Page 66: ...66 ...
Page 72: ...72 ...
Page 75: ...Appendix A ABB IP configuration tool for FMBT 21 75 ...
Page 76: ...76 ...
Page 80: ...80 ...
Page 84: ...84 Appendix D FMBT 21 configuration web pages ...
Page 90: ...Access to web pages is now enabled 90 Appendix D FMBT 21 configuration web pages ...