![ABB FBIP-21 BACnet/IP User Manual Download Page 67](http://html.mh-extra.com/html/abb/fbip-21-bacnet-ip/fbip-21-bacnet-ip_user-manual_4038067.webp)
Note: These settings are available only through web pages. When you select to disable
the web page, a warning appears to confirm before you can save the selection.
Or, you can use the web page password. See
Enable web page access after it was
It is recommended to disable all services that are not used after commissioning.
Configuring SNTP
Simple Network Time Protocol (SNTP) can be used to synchronize drive time with a
network time server. When SNTP is enabled, FBIP-21 will request the time from
configured server at a given interval. To receive this time synchronization, you must
configure the drive with parameter 96.20 time sync primary source. The table below
shows the settings for SNTP:
Value
Description
Settings
Default: 30 seconds
Interval to request time from server.
SNTP update interval
Minimum: 30
seconds
-1440...1440
minutes
Time offset to the time received from SNTP.
Note: SNTP time offset change does not need a
reboot.
SNTP time offset to UTC
Appendix C - FBIP-21 configuration web pages 67