![ABB FBIP-21 BACnet/IP User Manual Download Page 54](http://html.mh-extra.com/html/abb/fbip-21-bacnet-ip/fbip-21-bacnet-ip_user-manual_4038054.webp)
General conditions
Into an option slot on the drive control unit
Installation
IP20
Degree of protection
The ambient conditions specified for the drive in its manuals are applicable.
Ambient conditions
Cardboard. Plastic wrapping: Antistatic air bubble sheet (PE).
Package
Three bicolor LEDs (HOST, MODULE, NETWORK/NET)
Indicators
A 20-pin connector to the drive
Connectors
RJ-45 connector to Ethernet (X1)
RJ-45 connector for chaining another adapter module (X2)
+3.3 V ±5% max. 400 mA (supplied by the drive)
Power supply
Complies with EMC standard EN 61800-3:2004
Compliance
Printed circuit board conformal coated
BACnet link
Ethernet Standard IEEE 802.3 and IEEE 802.3u devices
Compatible devices
10BASE-TX or 100Base-TX with Autonegotiation and Auto-MDIX (Auto-cros-
sover)
Medium
• Wiring: CAT5/6 UTP, CAT5/6 FTP, CAT5/6 STP
• Connector: RJ-45
• Termination: Internal
• Maximum segment length: 100 m / 328 ft
Bus or star.
Topology
Max. 50 nodes allowed for FBIP-21 in a daisy chain topology.
10 Mbps or 100 Mbps.
Transfer rate
Half or full duplex
Serial communication
type
BACnet/IP
Protocol
TCP and UDP service ports
There are multiple in-bound and out-bound network services running on the FBIP-21.
Purpose
Service
Port
DHCP client.
DHCP
68 (UDP)
Note: Used only when IP configuration
method is selected as Dyn IP HFCP.
BACnet IP protocol.
BACnet
47808 (UDP)
Open source licenses
IwIP is licensed under the BSD license. Copyright (c) 2001-2004 Swedish Institute of
Computer Science. All rights reserved.
54 Technical data
Summary of Contents for FBIP-21 BACnet/IP
Page 2: ......
Page 4: ......
Page 8: ...8 ...
Page 14: ...14 ...
Page 38: ...38 ...
Page 50: ...50 ...
Page 58: ...58 ...
Page 62: ...62 ...
Page 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Page 72: ...72 Appendix D BACnet conformance certificate ...